Pipe Thermal Resistance Calculator

Calculate steady radial conduction resistance of a cylindrical pipe wall.

Your pipe & operating inputs

mm
mm
m
W/(m·K)

Starting values are editable examples. Verify actual bore, fluid state and model assumptions. Dimension switching converts only the labelled length fields; flow and property units stay as printed.

Reset

Your result

Ready to calculate

Enter your values and press Calculate. The result will open on the calculation page.

Published references · Clear assumptions · No sign-up

The method

Formula and calculation steps

Rwall=ln(ro/ri)/(2πkL).

Calculate steady radial conduction resistance of a cylindrical pipe wall.

  1. Confirm the fluid state, geometry, flow regime and units.
  2. Enter actual dimensions and justified operating conditions.
  3. Submit the form, then interpret the result with the assumptions and limits below.

Constant conductivity, no contact or fluid-film resistance; this is K/W for the entered full length, not plane-wall thickness/k.

Pipe Thermal Resistance: assumptions and applications

Calculate steady radial conduction resistance of a cylindrical pipe wall. Constant conductivity, no contact or fluid-film resistance; this is K/W for the entered full length, not plane-wall thickness/k.

Use the actual measured bore rather than assuming a nominal pipe label equals its inside diameter. Schedule, lining, corrosion and deposits can change the effective flow area. Enter the applicable fluid properties at the operating temperature.

A flow rate, velocity, pressure difference and capacity describe different physical quantities. The stated model determines which additional measurements are needed. The calculated examples below vary one input while holding all other printed values fixed.

Check the numbers

Pipe Thermal Resistance Calculator: calculated examples

These scenarios are computed with the same method as the form. They are not product recommendations, code design values or complete standards tables.

Worked example with stated inputs

Dimension units = Metric (m / mm); Outside diameter = 60.3 mm; Wall thickness = 3.91 mm; Straight pipe length = 10 m; Pipe conductivity = 45 W/(m·K).

OutputComputed result
Pipe wall radial resistance4.912581e-5 K/W

How the stated input changes the result

ScenarioChanged input / basisResult
5 mStraight pipe length9.825162e-5 K/W
7.5 mStraight pipe length6.550108e-5 K/W
10 mStraight pipe length4.912581e-5 K/W
12.5 mStraight pipe length3.930065e-5 K/W
15 mStraight pipe length3.275054e-5 K/W
20 mStraight pipe length2.456291e-5 K/W

Unchanged inputs use: Dimension units = Metric (m / mm); Outside diameter = 60.3 mm; Wall thickness = 3.91 mm; Straight pipe length = 10 m; Pipe conductivity = 45 W/(m·K). Results retain the model limitations described above.

Common questions

What is the main limitation of this calculation?

Constant conductivity, no contact or fluid-film resistance; this is K/W for the entered full length, not plane-wall thickness/k.

How are the comparison-table numbers generated?

Each row changes the labelled straight pipe length from the worked example. The other printed inputs remain fixed. The table uses the same Rwall=ln(ro/ri)/(2πkL). method as the form.

How do I use this pipe thermal resistance calculator?

Calculate steady radial conduction resistance of a cylindrical pipe wall. Rwall=ln(ro/ri)/(2πkL).

Can I calculate in metric and imperial units?

The dimension selector converts the labelled length inputs. Flow and property inputs retain their explicitly printed units. Results include related units where meaningful; US gallons and Imperial gallons are different units.

Can I export this calculation to Excel?

Calculate first, then use Export CSV for results and inputs. This is a numeric text export, not an Excel formula workbook, desktop application or certified engineering report.

What do the starting values mean?

They are editable numerical examples. Actual bore, fluid state, roughness, geometry and boundary conditions must match the installation. A calculated result is not a pressure rating or code sizing approval.

Where are the formula sources?

The sources below show plain-text addresses. Equations, examples and tables are stored in these pages; the calculator does not fetch source websites or JSON data files during use.

Formula sources and references

References support the underlying methods and units. Chosen example inputs are not universal recommendations, supplier ratings, market prices or code limits.

  • US DOE Fundamentals Handbook 1012/2-92: Heat Transfer, HT-02 pp. 11-27https://www.energy.gov/sites/default/files/2026-04/DOE-HDBK-1012-92_VOL2.pdf
  • NIST Guide to the SI: conversion factorshttps://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors