Pipe calculators / Heat transfer & expansion
Define the pipe. Follow the flow.
Insulated Pipe Heat Loss Calculator
Calculate cylindrical insulation conduction and outer convection heat transfer.
Your pipe & operating inputs
Your result
Ready to calculateEnter your values and press Calculate. The result will open on the calculation page.
Published references · Clear assumptions · No sign-up
The method
Formula and calculation steps
Rins=ln(r2/r1)/(2πkL); Rconv=1/(h 2πr2 L); heat=(Tpipe−Tair)/(Rins+Rconv).
Calculate cylindrical insulation conduction and outer convection heat transfer.
- Confirm the fluid state, geometry, flow regime and units.
- Enter actual dimensions and justified operating conditions.
- Submit the form, then interpret the result with the assumptions and limits below.
Inner boundary is the supplied bare-pipe outer surface temperature. Radiation, pipe-wall resistance and internal film are omitted; conductivity and h are supplied constants.
Insulated Pipe Heat Loss: assumptions and applications
Calculate cylindrical insulation conduction and outer convection heat transfer. Inner boundary is the supplied bare-pipe outer surface temperature. Radiation, pipe-wall resistance and internal film are omitted; conductivity and h are supplied constants.
Use the actual measured bore rather than assuming a nominal pipe label equals its inside diameter. Schedule, lining, corrosion and deposits can change the effective flow area. Enter the applicable fluid properties at the operating temperature.
A flow rate, velocity, pressure difference and capacity describe different physical quantities. The stated model determines which additional measurements are needed. The calculated examples below vary one input while holding all other printed values fixed.
Continue with: Bare Pipe Heat Loss Calculator · Pipe Thermal Resistance Calculator · Pipe Outlet Temperature Calculator · Pipe Water Heating Time Calculator
Check the numbers
Insulated Pipe Heat Loss Calculator: calculated examples
These scenarios are computed with the same method as the form. They are not product recommendations, code design values or complete standards tables.
Worked example with stated inputs
Dimension units = Metric (m / mm); Bare pipe outside diameter = 60.3 mm; Straight pipe length = 10 m; Insulation thickness = 25 mm; Insulation conductivity = 0.04 W/(m·K); Outside convection coefficient = 10 W/(m²·K); Pipe outer surface temperature = 100 °C; Ambient air temperature = 20 °C.
| Output | Computed result |
|---|---|
| Signed outward insulated-pipe heat transfer | 297.252435 W |
| Heat per metre | 29.725244 W/m |
| Insulation resistance | 0.240273 K/W |
| Outside convection resistance | 0.028859 K/W |
| Critical insulation radius | 4 mm |
How the stated input changes the result
| Scenario | Changed input / basis | Result |
|---|---|---|
| 5 m | Straight pipe length | 148.626218 W |
| 7.5 m | Straight pipe length | 222.939326 W |
| 10 m | Straight pipe length | 297.252435 W |
| 12.5 m | Straight pipe length | 371.565544 W |
| 15 m | Straight pipe length | 445.878653 W |
| 20 m | Straight pipe length | 594.50487 W |
Unchanged inputs use: Dimension units = Metric (m / mm); Bare pipe outside diameter = 60.3 mm; Straight pipe length = 10 m; Insulation thickness = 25 mm; Insulation conductivity = 0.04 W/(m·K); Outside convection coefficient = 10 W/(m²·K); Pipe outer surface temperature = 100 °C; Ambient air temperature = 20 °C. Results retain the model limitations described above.
Common questions
What is the main limitation of this calculation?
Inner boundary is the supplied bare-pipe outer surface temperature. Radiation, pipe-wall resistance and internal film are omitted; conductivity and h are supplied constants.
How are the comparison-table numbers generated?
Each row changes the labelled straight pipe length from the worked example. The other printed inputs remain fixed. The table uses the same Rins=ln(r2/r1)/(2πkL); Rconv=1/(h 2πr2 L); heat=(Tpipe−Tair)/(Rins+Rconv). method as the form.
How do I use this insulated pipe heat loss calculator?
Calculate cylindrical insulation conduction and outer convection heat transfer. Rins=ln(r2/r1)/(2πkL); Rconv=1/(h 2πr2 L); heat=(Tpipe−Tair)/(Rins+Rconv).
Can I calculate in metric and imperial units?
The dimension selector converts the labelled length inputs. Flow and property inputs retain their explicitly printed units. Results include related units where meaningful; US gallons and Imperial gallons are different units.
Can I export this calculation to Excel?
Calculate first, then use Export CSV for results and inputs. This is a numeric text export, not an Excel formula workbook, desktop application or certified engineering report.
What do the starting values mean?
They are editable numerical examples. Actual bore, fluid state, roughness, geometry and boundary conditions must match the installation. A calculated result is not a pressure rating or code sizing approval.
Where are the formula sources?
The sources below show plain-text addresses. Equations, examples and tables are stored in these pages; the calculator does not fetch source websites or JSON data files during use.
Related calculators
Formula sources and references
References support the underlying methods and units. Chosen example inputs are not universal recommendations, supplier ratings, market prices or code limits.
- US DOE Fundamentals Handbook 1012/2-92: Heat Transfer, HT-02 pp. 11-27https://www.energy.gov/sites/default/files/2026-04/DOE-HDBK-1012-92_VOL2.pdf
- NIST Guide to the SI: conversion factorshttps://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors